6-73 Terminal 45 Output Min Scale
Default value: 0.00% Parameter type: Range (0.00–200.00%)
Setup: All setups Conversion index: -2
Data type: Uint16 Change during operation: True
Scale for the minimum output (0 or 4 mA) of the analog signal at terminal 45. Set the value to be the percentage of the full range of the
variable selected in parameter 6-71 Terminal 45 Analog Output.
6-74 Terminal 45 Output Max Scale
Default value: 100.00% Parameter type: Range (0.00–200.00%)
Setup: All setups Conversion index: -2
Data type: Uint16 Change during operation: True
Scale for the maximum output (20 mA) of the analog signal at terminal 45. Set the value to be the percentage of the full range of the
variable selected in parameter 6-71 Terminal 45 Analog Output.
6-76 Terminal 45 Output Bus Control
Default value: 0 Parameter type: Range (0–16384)
Setup: All setups Conversion index: 0
Data type: Uint16 Change during operation: True
Hold the level of analog output if controlled by bus.
4.7.6 6-9* Analog/Digital Output 42
Parameters for configuring the limits for analog/digital output terminal 42. Analog outputs are current outputs: 0/4–20 mA. Resolution
on analog outputs is 12 bit. Analog output terminals can also be set up as digital output.
6-90 Terminal 42 Mode
Default value: [0] 0-20 mA Parameter type: Option
Setup: All setups Conversion index: –
Data type: Uint8 Change during operation: True
Set terminal 42 to act as analog output or as digital output.
Option Name
[0] 0-20 mA
[1] 4-20 mA
[2] Digital Output
6-91 Terminal 42 Analog Output
Default value: [0] No operation Parameter type: Option