Programming Guide | VLT® AutomationDrive FC 360
Setup: All setups Conversion index: 0
Data type: Uint16 Change during operation: True
Readout of revision count.
4.11 Parameter Group 12-** Ethernet
4.11.1 More Information
For more information about Ethernet parameter descriptions, see the VLT® AutomationDrive FC 360 PROFINET Programming Guide.
 NOTICE
Parameter Group 12-** Ethernet is only valid when PROFINET is used.
4.11.2 12-0* IP Settings
12-00 IP Address Assignment
Default value: [10] DCP Parameter type: Option
Setup: 1 setup Conversion index: –
Data type: Uint8 Change during operation: True
Select the IP address assignment method.
Option Name Description
[0] MANUAL IP address can be set in parameter 12-01
IP Address.
[1] DHCP IP address is assigned via DHCP server.
[2] BOOTP IP address is assigned via BOOTP server.
[10] DCP DCP is assigned via the DCP protocol.
[20] From node ID
12-01 IP Address
Default value: 0 Parameter type: Range (0–4294967295)
Setup: 1 setup Conversion index: 0
Data type: OctStr Change during operation: True
Configure the IP address of the option. Read-only if parameter 12-00 IP Address Assignment is set to [1] DHCP, [2] BOOTP, or via DIP
switches.
12-02 Subnet Mask
Default value: 0 Parameter type: Range (0–4294967295)
Setup: 1 setup Conversion index: 0
Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507 | 203