 WARNING
MOTOR MAY RUN AT HIGH SPEED
The AMA function can be done without the motor running. If [7] Enable Inertia Run in parameter 1-29 Automatic Motor Adaption
(AMA) is selected, the motor may run at high speed.
l Only qualified personnel must perform AMA.
3.2.3.2 Running AMA Using the Numeric LCP
1. By default parameter setting, connect terminals 12 and 27 before running AMA.
2. Enter the Main Menu.
3. Go to parameter group 1-** Load and Motor.
4. Press [OK].
5. Set motor parameters using nameplate data for parameter group 1-2* Motor Data.
6. Set parameter 1-39 Motor Poles for IM and PM.
7. Set parameter 1-40 Back EMF at 1000 RPM for PM.
8. Set motor cable length in parameter 1-42 Motor Cable Length.
9. Go to parameter 1-29 Automatic Motor Adaptation (AMA).
10. Press [OK].
11. Select [1] Enable complete AMA.
12. Press [OK].
13. Press [Hand On] to activate AMA.
14. The test runs automatically and indicates when it is complete.

Depending on the power size, the AMA takes 3–10 minutes to complete.