Option Name Description
[2] Copy from setup 2 Copy from setup 2 to setup 1.
[9] Copy from factory setup Copy factory setting to programming
setup (selected in parameter 0-11
Programming Set-up).
4.1.8 0-6* Password
0-60 Main Menu Password
Default value: 0 Parameter type: Range (0–999)
Setup: 1 setup Conversion index: 0
Data type: Uint16 Change during operation: True
Define the password for access to the Main Menu via the [Main Menu] key. Setting values to 0 disables the password function.
4.2 Parameter Group 1-** Load and Motor
4.2.1 1-0* General Settings
1-00 Configuration Mode
Default value: [0] Open Loop Parameter type: Option
Setup: All setups Conversion index: –
Data type: Uint8 Change during operation: True
Select the application control principle to be used when a remote reference (that is, via analog input or fieldbus) is active.
Option Name Description
[0] Open Loop Enables speed control (without feedback
signal from motor) with automatic slip
compensation for almost constant speed
at varying loads. Compensations are
active, but can be disabled in parameter
group 1-** Load and Motor.
[1] Speed Closed Loop Enables speed closed loop control with
feedback. For increased speed accuracy,
provide a feedback signal and set the
Speed PID control. The speed control
parameters are set in parameter group
7-0* Speed PID Control.
[2] Torque Closed Loop Enables torque closed loop control with
speed feedback. Only possible when
option [1] VVC+ is selected in parameter
1-01 Motor Control Principle.
48 | Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507
Programming Guide | VLT® AutomationDrive FC 360