Programming Guide | VLT® AutomationDrive FC 360
14-64 Dead Time Compensation Zero Current Level
Default value: [0] Disabled Parameter type: Option
Setup: All setups Conversion index: –
Data type: Uint8 Change during operation: False
Select [1] Enabled to minimize the motor torque ripple when using a long motor cable.
Option Name
[0] Disabled
[1] Enabled
14-65 Speed Derate Dead Time Compensation
Default value: Size related Parameter type: Range (20–1000 Hz)
Setup: All setups Conversion index: 0
Data type: Uint16 Change during operation: False
Deadtime compensation level is reduced linearly versus output frequency from the maximum level set in parameter 14-07 Dead Time
Compensation Level to a minimum level set in this parameter.
4.13.8 14-7* Compatibility
14-70 Compatibility Selections
Default value: [0] No Function Parameter type: Option
Setup: 1 setup Conversion index: –
Data type: Uint8 Change during operation: False
Select the compatibility mode for the drive.
Option Name
[0] No Function
[10] Status Par. VLT 5000
[11] Status Par. and MAV VLT 5000
[31] Customize Converter 1
[32] Customize Converter 2
[33] Customize Converter 3
14-75 Customize Converter Readout
Default value: 0 Parameter type: Range (0–20)
Setup: 1 setup Conversion index: 0