Data type: VisStr Change during operation: False
A readout parameter to show which converter is running.
4.13.9 14-8* Options
14-89 Option Detection
Default value: [0] Protect Option Config. Parameter type: Option
Setup: 1 setup Conversion index: –
Data type: Uint8 Change during operation: True
Select the behavior when an option change is detected. This parameter returns to [0] Protect Option Config. after an option change.
Option Name Description
[0] Protect Option Config. Freeze the current settings and avoids
unwanted changes when missing or
defective options are detected.
[1] Enable Option Change Settings can be changed when the system
configuration is being modified.
4.13.10 14-9* Fault Settings
Use the parameters to configure the fault settings.
14-90 Fault Level
Default value: [3] Trip Lock Parameter type: Option, Array [32]
Setup: All setups Conversion index: –
Data type: Uint8 Change during operation: True
Use this parameter to customize fault levels. The type of the parameter is index, see Table 20.
Option Name Description
[0] Off
[1] Warning
[2] Trip
[3] Trip Lock Alarm is set to trip lock.
246 | Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507
Programming Guide | VLT® AutomationDrive FC 360