4.16.2 17-1* Inc.Enc.Interface
 NOTICE
This parameter group is only valid when VLT
®
Encoder Input MCB 102 is installed.
17-10 Signal Type
Default value: [1] RS422 (5 V TTL) Parameter type: Option
Setup: All setups Conversion index: –
Data type: Uint8 Change during operation: False
Select the incremental type (A/B channel) of the encoder in use. Find the information on the encoder datasheet.
Option Name
[0] None
[1] RS422 (5 V TTL)
[2] Sinusoidal 1Vpp
17-11 Resolution (PPR)
Default value: 1024 Parameter type: Range (10–16384)
Setup: All setups Conversion index: 0
Data type: Uint16 Change during operation: False
Enter the resolution of the incremental track, which is the number of pulses or periods per revolution.
4.16.3 17-2* Abs. Enc. Interface
 NOTICE
This parameter group is only valid when VLT
®
Encoder Input MCB 102 is installed.
17-20 Protocol Selection
Default value: [0] None Parameter type: Option
Setup: All setups Conversion index: –
Data type: Uint8 Change during operation: False
Select the appropriate type of connected absolute encoder. If an incremental encoder is used, set parameter 17-10 Signal Type.
Option Name
[0] None
[4] SSI