Select [0] Disabled to avoid accidental stop or reset of the drive from LCP. Setting can be locked by parameter 0-60 Main Menu Password.
Option Name Description
[0] Disabled Avoid accidental stop or reset of the drive
from LCP.
[1] Enabled [Off/Reset] mode is enabled.
[7] Enable Reset Only Only Reset is enabled.
4.1.7 0-5* Copy/Save
0-50 LCP Copy
Default value: [0] No copy Parameter type: Option
Setup: 1 setup Conversion index: –
Data type: Uint8 Change during operation: False
Copy parameters from and to the LCP.
Option Name Description
[0] No copy No function.
[1] All to LCP Copy all parameters in all set-ups from
the drive memory to the LCP. For service
purposes, copy all parameters to the LCP
after commissioning.
[2] All from LCP Copy all parameters in all set-ups from the
LCP memory to the drive memory.
[3] Size indep. from LCP Copy only the parameters that are
independent of the motor size. This
selection can be used to program several
drives with the same function without
disturbing motor data that is already set.
0-51 Set-up Copy
Default value: [0] No copy Parameter type: Option
Setup: 1 setup Conversion index: –
Data type: Uint8 Change during operation: False
Copy parameters between factory settings and the parameter setups.
Option Name Description
[0] No copy No function.
[1] Copy from setup 1 Copy from setup 1 to setup 2.