Programming Guide | VLT® AutomationDrive FC 360
8-07 Diagnosis Trigger
Default value: [0] Disable Parameter type: Option
Setup: 1 setup Conversion index: –
Data type: Uint8 Change during operation: True
Enable or disable the sending extended diagnosis data (EDD) function.
Option Name Description
[0] Disable Send no extended diagnosis data (EDD).
[1] Trigger on alarms Send EDD via alarms.
[2] Trigger alarm/warn. Send EDD via alarms or warnings in
parameter 16-90 Alarm Word, parameter
9-53 PROFIBUS Warning Word, or
parameter 16-92 Warning Word.
4.9.2 8-1* Ctrl. Word Settings
8-10 Control Word Profile
Default value: [0] FC profile Parameter type: Option
Setup: All setups Conversion index: –
Data type: Uint8 Change during operation: True
Select the interpretation of the control and status words corresponding to the installed fieldbus. Only the selections valid for the
installed fieldbus are visible in the LCP display.
Option Name
[0] FC profile
[1] PROFIdrive profile
8-14 Configurable Control Word CTW
Default value: [1] Profile default Parameter type: Option, Array [16]
Setup: All setups Conversion index: –
Data type: Uint8 Change during operation: True
The control word has 16 bits (0-15). Bits 10 and 12-15 are configurable.
Option Name
[0] None
[1] Profile default
[2] CTW Valid, active low
Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507 | 173