Enter the limit for the motor speed when the rotation direction is clockwise.
4-94 Negative Speed Limit [Hz]
Default value: Size related Parameter type: Range (0.0–500.0 Hz)
Setup: All setups Conversion index: -1
Data type: Uint16 Change during operation: True
Enter the limit for the motor speed when the rotation direction is counterclockwise.
4-95 Positive Torque limit
Default value: Size related Parameter type: Range (0.0–160.0%)
Setup: All setups Conversion index: -1
Data type: Uint16 Change during operation: True
Enter the limit for the motor torque when the torque direction is clockwise.
4-96 Negative Torque limit
Default value: Size related Parameter type: Range (0.0–160.0%)
Setup: All setups Conversion index: -1
Data type: Uint16 Change during operation: True
Enter the limit for the motor torque when the torque direction is counterclockwise.
4.6 Parameter Group 5-** Digital In/Out
4.6.1 5-0* Digital I/O mode
Parameters for configuring the input and output using NPN and PNP.
5-00 Digital Input Mode
Default value: [0] PNP Parameter type: Option
Setup: 1 setup Conversion index:
Data type: Uint8 Change during operation: False
Set NPN or PNP mode for digital inputs.
Option Name Description
[0] PNP Action on positive directional pulses (0).
PNP systems are pulled down to ground
(GND).
[1] NPN Action on negative directional pulses
(1). NPN systems are pulled up to +24 V,
internally in the drive.
110 | Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507