16-86 FC Port REF 1
Default value: 0 Parameter type: Range (-32768–32767)
Setup: 1 setup Conversion index: 0
Data type: Int16 Change during operation: True
View the last received reference from the FC port.
16-88 Fieldbus Torque FF.
Default value: 0 Parameter type: Range (-32768–32767)
Setup: 1 setup Conversion index: 0
Data type: Int16 Change during operation: True
Set the fieldbus torque feedforward.
4.15.7 16-9* Diagnosis Readouts
Use the parameters to show alarm, warning, and extended status words.
16-90 Alarm Word
Default value: 0 Parameter type: Range (0–0xFFFFFFFFUL)
Setup: 1 setup Conversion index: 0
Data type: Uint32 Change during operation: True
View the alarm word sent via the serial communication port in hex code.
16-91 Alarm Word 2
Default value: 0 Parameter type: Range (0–0xFFFFFFFFUL)
Setup: 1 setup Conversion index: 0
Data type: Uint32 Change during operation: True
View the alarm word 2 sent via the serial communication port in hex code.
16-92 Warning Word
Default value: 0 Parameter type: Range (0–0xFFFFFFFFUL)
Setup: 1 setup Conversion index: 0
Data type: Uint32 Change during operation: True
View the warning word sent via the serial communication port in hex code.
16-93 Warning Word 2
Default value: 0 Parameter type: Range (0–0xFFFFFFFFUL)
Setup: 1 setup Conversion index: 0
Data type: Uint32 Change during operation: True
264 | Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507