Option Name Description
[0] Disabled No OVC required.
[1] Enabled (not at stop) Activate OVC except when using a stop
signal to stop the drive.
[2] Enabled Activate OVC.
CAUTION
PERSONAL INJURY AND
EQUIPMENT DAMAGE
Enabling OVC in hoisting
applications may lead to personal
injuries and equipment damage.
l DO NOT enable OVC in
hoisting applications.
2-19 Over-voltage Gain
Default value: 100% Parameter type: Range (0–1000%)
Setup: All setups Conversion index: 0
Data type: Uint16 Change during operation: True
This parameter enables the user to fine-tune the Over-voltage gain for parameter 2-17 Over-voltage Control. It is not necessary to
change this parameter for normal applications.
4.3.3 2-2* Mechanical Brake
2-20 Release Brake Current
Default value: 0.00 A Parameter type: Range (0.00–100.00 A)
Setup: All setups Conversion index: -2
Data type: Uint32 Change during operation: True
Set the motor current for release of the mechanical brake when a start condition is present.
NOTICE
When mechanical brake control output is selected, but no mechanical brake is connected, the function does not work by default
setting due to too low motor current.
2-22 Activate Brake Speed [Hz]
Default value: 0.0 Hz Parameter type: Range (0.0–400.0 Hz)
Setup: All setups Conversion index: -1
Data type: Uint16 Change during operation: True