Option Name
[4] PID error inverse
[5] PID resets I part
[6] PID enable
8-19 Product Code
Default value: Size related Parameter type: Range (0–2147483647), Array
[2]
Setup: 1 setup Conversion index: 0
Data type: Uint32 Change during operation: True
Select 0 to read out the actual fieldbus product code according to the mounted fieldbus option. Select 1 to read out the actual vendor ID.
4.9.3 8-3* FC Port Settings
8-30 Protocol
Default value: [0] FC Parameter type: Option
Setup: 1 setup Conversion index: –
Data type: Uint8 Change during operation: True
Select the protocol for the integrated RS485 port.
Option Name Description
[0] FC Communication according to the FC
protocol.
[1] Modbus RTU Communication according to the Modbus
RTU protocol.
8-31 Address
Default value: 1 Parameter type: Range (0–247)
Setup: 1 setup Conversion index: 0
Data type: Uint8 Change during operation: True
Enter the address for the RS485 port. Valid range: 1–126 for FC-bus, or 1–247 for Modbus.
8-32 Baud Rate
Default value: Size related Parameter type: Option
Setup: 1 setup Conversion index: –
Data type: Uint8 Change during operation: True
Select the baud rate for the RS485 port.
174 | Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507
Programming Guide | VLT® AutomationDrive FC 360

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 360

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 360 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 360 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 360
CategoryDC Drives
LanguageEnglish

Related product manuals