EasyManuals Logo

Danfoss VLT AutomationDrive FC 360 Programming Guide

Danfoss VLT AutomationDrive FC 360
340 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #177 background imageLoading...
Page #177 background image
Programming Guide | VLT® AutomationDrive FC 360
 NOTICE
For some of the protocols, not all options are available.
Option Name
[0] 2400 Baud
[1] 4800 Baud
[2] 9600 Baud
[3] 19200 Baud
[4] 38400 Baud
[5] 57600 Baud
[6] 76800 Baud
[7] 115200 Baud
8-33 Parity/Stop Bits
Default value: Size related Parameter type: Option
Setup: 1 setup Conversion index: –
Data type: Uint8 Change during operation: True
Parity and Stop Bits for the protocol using the FC Port. For some of the protocols, not all options are available.
Option Name
[0] Even Parity, 1 Stop Bit
[1] Odd Parity, 1 Stop Bit
[2] No Parity, 1 Stop Bit
[3] No Parity, 2 Stop Bits
8-35 Minimum Response Delay
Default value: 0.010 s Parameter type: Range (0.001–0.500 s)
Setup: 1 setup Conversion index: -3
Data type: Uint16 Change during operation: True
Specify the minimum delay time between receiving a request and sending a response. This is used for overcoming modem turn-around
delays.
8-36 Maximum Response Delay
Default value: Size related Parameter type: Range (0.100–10.000 s)
Setup: 1 setup Conversion index: -3
Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507 | 175

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 360

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 360 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 360 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 360
CategoryDC Drives
LanguageEnglish

Related product manuals