Programming Guide | VLT® AutomationDrive FC 360
 NOTICE
For some of the protocols, not all options are available.
Option Name
[0] 2400 Baud
[1] 4800 Baud
[2] 9600 Baud
[3] 19200 Baud
[4] 38400 Baud
[5] 57600 Baud
[6] 76800 Baud
[7] 115200 Baud
8-33 Parity/Stop Bits
Default value: Size related Parameter type: Option
Setup: 1 setup Conversion index: –
Data type: Uint8 Change during operation: True
Parity and Stop Bits for the protocol using the FC Port. For some of the protocols, not all options are available.
Option Name
[0] Even Parity, 1 Stop Bit
[1] Odd Parity, 1 Stop Bit
[2] No Parity, 1 Stop Bit
[3] No Parity, 2 Stop Bits
8-35 Minimum Response Delay
Default value: 0.010 s Parameter type: Range (0.001–0.500 s)
Setup: 1 setup Conversion index: -3
Data type: Uint16 Change during operation: True
Specify the minimum delay time between receiving a request and sending a response. This is used for overcoming modem turn-around
delays.
8-36 Maximum Response Delay
Default value: Size related Parameter type: Range (0.100–10.000 s)
Setup: 1 setup Conversion index: -3
Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507 | 175