EasyManuals Logo

Danfoss VLT AutomationDrive FC 360 Programming Guide

Danfoss VLT AutomationDrive FC 360
340 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #69 background imageLoading...
Page #69 background image
Programming Guide | VLT® AutomationDrive FC 360
1-57 Torque Estimation Time Constant
Default value: 150 ms Parameter type: Range (50–1000 ms)
Setup: All setups Conversion index: 0
Data type: Uint16 Change during operation: True
Set the time constant for the torque estimation below model change point in Flux Sensorless.
4.2.7 1-6* Load Depen. Setting
Parameters for adjusting the load-dependent motor settings.
1-60 Low Speed Load Compensation
Default value: 100% Parameter type: Range (0–300%)
Setup: All setups Conversion index: 0
Data type: Int16 Change during operation: True
Enter the low-speed voltage compensation value in percent. This parameter is used for optimizing the low-speed load performance. This
parameter is only active if parameter 1-10 Motor Construction = [0] Asynchron.
1-61 High Speed Load Compensation
Default value: 100% Parameter type: Range (0–300%)
Setup: All setups Conversion index: 0
Data type: Int16 Change during operation: True
Enter the high-speed voltage compensation value in percent. This parameter is used for optimizing the high-speed load performance.
This parameter is only active if parameter 1-10 Motor Construction = [0] Asynchron.
1-62 Slip Compensation
Default value: Size related Parameter type: Range (-400–400%)
Setup: All setups Conversion index: 0
Data type: Int16 Change during operation: True
Enter the % value for slip compensation to compensate for tolerance in the value of n
M, N
. Slip compensation is calculated automatically,
that is, based on the nominal motor speed n
M, N
.
1-63 Slip Compensation Time Constant
Default value: 0.10 s Parameter type: Range (0.05–5.00 s)
Setup: All setups Conversion index: -2
Data type: Uint16 Change during operation: True
Enter the slip compensation reaction speed. A high value results in slow reaction, and a low value results in quick reaction. If low-
frequency resonance problems occur, use a longer time setting.
Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507 | 67

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 360

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 360 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 360 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 360
CategoryDC Drives
LanguageEnglish

Related product manuals