Programming Guide | VLT® AutomationDrive FC 360
Option Name
[0] Off
[2] Stop
[5] Stop and trip
4.24.3 35-1* Temp. Input X48/4
35-14 Term. X48/4 Filter Time Constant
Default value: 0.005 s Parameter type: Range (0.005–10.000 s)
Setup: All setups Conversion index: -3
Data type: Uint16 Change during operation: True
Enter the filter time constant. This is a first-order digital lowpass filter time constant for suppressing electrical noise in terminal X48/4. A
high time constant value improves dampening but also increases the time delay through the filter.
35-15 Term. X48/4 Temp. Monitor
Default value: [0] Disabled Parameter type: Option
Setup: All setups Conversion index: –
Data type: Uint8 Change during operation: True
This parameter gives the possibility of enabling or disabling the temperature monitor for terminal X48/4. The temperature limits can be
set in parameter 35-16 Term. X48/4 Low Temp. Limit/parameter 35-17 Term. X48/4 High Temp. Limit.
Option Name
[0] Disabled
[1] Enabled
35-16 Term. X48/4 Low Temp. Limit
Default value: -50 Parameter type: Range (-50–204)
Setup: All setups Conversion index: 0
Data type: Int16 Change during operation: True
Enter the minimum temperature reading that is expected for normal operation of the temperature sensor at terminal X48/4.
35-17 Term. X48/4 High Temp. Limit
Default value: 204 Parameter type: Range (-50–204)
Setup: All setups Conversion index: 0
Data type: Int16 Change during operation: True
Enter the maximum temperature reading that is expected for normal operation of the temperature sensor at terminal X48/4.
Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507 | 295