Setup: All setups Conversion index: -2
Data type: Uint32 Change during operation: True
Control the dynamics of the feedforward signal when ramping down.
7-56 Process PID Ref. Filter Time
Default value: 0.001 s Parameter type: Range (0.001–1.000 s)
Setup: All setups Conversion index: -3
Data type: Uint16 Change during operation: True
Set a time constant for the reference first-order low-pass filter. The low-pass filter improves steady-state performance and dampens
oscillations on the reference/feedback signals. However, severe filtering can be detrimental to dynamic performance.
7-57 Process PID Fb. Filter Time
Default value: 0.001 s Parameter type: Range (0.001–1.000 s)
Setup: All setups Conversion index: -3
Data type: Uint16 Change during operation: True
Set a time constant for the feedback first-order low-pass filter. The low-pass filter improves steady-state performance and dampens
oscillations on the reference/feedback signals. However, severe filtering can be detrimental to dynamic performance.
4.8.7 7-6* Feedback Conversion
Use the parameter group to configure conversions for feedback signals.
7-60 Feedback 1 Conversion
Default value: [0] Linear Parameter type: Option
Setup: All setups Conversion index: –
Data type: Uint8 Change during operation: True
Select a conversion for the feedback 1 signal. Select [0] Linear to leave the feedback signal unchanged.
Option Name
[0] Linear
[1] Square root
7-62 Feedback 2 Conversion
Default value: [0] Linear Parameter type: Option
Setup: All setups Conversion index: –
Data type: Uint8 Change during operation: True
Select a conversion for the feedback 2 signal. Select [0] Linear to leave the feedback signal unchanged.
170 | Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507
Programming Guide | VLT® AutomationDrive FC 360

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 360

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 360 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 360 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 360
CategoryDC Drives
LanguageEnglish

Related product manuals