Setup: All setups Conversion index: -2
Data type: Uint32 Change during operation: True
Control the dynamics of the feedforward signal when ramping down.
7-56 Process PID Ref. Filter Time
Default value: 0.001 s Parameter type: Range (0.001–1.000 s)
Setup: All setups Conversion index: -3
Data type: Uint16 Change during operation: True
Set a time constant for the reference first-order low-pass filter. The low-pass filter improves steady-state performance and dampens
oscillations on the reference/feedback signals. However, severe filtering can be detrimental to dynamic performance.
7-57 Process PID Fb. Filter Time
Default value: 0.001 s Parameter type: Range (0.001–1.000 s)
Setup: All setups Conversion index: -3
Data type: Uint16 Change during operation: True
Set a time constant for the feedback first-order low-pass filter. The low-pass filter improves steady-state performance and dampens
oscillations on the reference/feedback signals. However, severe filtering can be detrimental to dynamic performance.
4.8.7 7-6* Feedback Conversion
Use the parameter group to configure conversions for feedback signals.
7-60 Feedback 1 Conversion
Default value: [0] Linear Parameter type: Option
Setup: All setups Conversion index: –
Data type: Uint8 Change during operation: True
Select a conversion for the feedback 1 signal. Select [0] Linear to leave the feedback signal unchanged.
Option Name
[0] Linear
[1] Square root
7-62 Feedback 2 Conversion
Default value: [0] Linear Parameter type: Option
Setup: All setups Conversion index: –
Data type: Uint8 Change during operation: True
Select a conversion for the feedback 2 signal. Select [0] Linear to leave the feedback signal unchanged.