Option Name
[0] Normal
[1] Mirror Port 1 to 2
[2] Mirror Port 2 to 1
[10] Port 1 disabled
[11] Port 2 disabled
[254] Mirror Int. Port to 1
[255] Mirror Int. Port to 2
12-98 Interface Counters
Default value: 4000 Parameter type: Range (0–4294967295), Array
[11]
Setup: All setups Conversion index: 0
Data type: Uint32 Change during operation: True
Read-only. Advanced interface counters from a built-in switch can be used for low-level troubleshooting. The parameter shows a sum of
port 1 + port 2.
12-99 Media Counters
Default value: 0 Parameter type: Range (0–4294967295), Array
[10]
Setup: All setups Conversion index: 0
Data type: Uint32 Change during operation: True
Read-only. Advanced interface counters from a built-in switch can be used for low-level troubleshooting. The parameter shows a sum of
port 1 + port 2.
4.12 Parameter Group 13-** Smart Logic
4.12.1 Smart Logic Control
Smart logic control (SLC) is a sequence of user-defined actions (see parameter 13-52 SL Controller Action) executed by the SLC when the
associated user-defined event (see parameter 13-51 SL Controller Event) is evaluated as true by the SLC. The condition for an event can
be a particular status, or that the output from a logic rule or a comparator operand becomes true. That leads to an associated action as
shown in the following illustration.
210 | Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507
Programming Guide | VLT® AutomationDrive FC 360