Programming Guide | VLAutomationDrive FC 360
4.5.2 4-2* Limit Factors
4-20 Torque Limit Factor Source
Default value: [0] No function Parameter type: Option
Setup: All setups Conversion index:
Data type: Uint8 Change during operation: True
Select an analog input for scaling the settings in parameter 4-16 Torque Limit Motor Mode and parameter 4-17 Torque Limit Generator
Mode 0–100% (or inverse). The signal levels corresponding to 0% and 100% are defined in the analog input scaling, for example
parameter group 6-1* Analog Input 1. This parameter is only active when parameter 1-00 Configuration Mode is set to [0] Open Loop or
[1] Speed Closed Loop.
Option Name
[0] No function
[2] Analog in 53
[4] Analog in 53 inv
[6] Analog in 54
[8] Analog in 54 inv
[18] Bus Control
4-21 Speed Limit Factor Source
Default value: [0] No function Parameter type: Option
Setup: All setups Conversion index:
Data type: Uint8 Change during operation: True
Select an analog input for scaling the settings in parameter 4-19 Max Output Frequency 0–100% (or inverse). The signal levels
corresponding to 0% and 100% are defined in the analog input scaling, for example parameter group 6-1* Analog Input 1. This
parameter is only active when parameter 1-00 Configuration Mode is in torque mode.
Option Name
[0] No function
[2] Analog in 53
[4] Analog in 53 inv
[6] Analog in 54
[8] Analog in 54 inv
[18] Bus Control
4-22 Break Away Boost
Default value: [0] Off Parameter type: Option
Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507 | 101