EasyManuals Logo
Home>Danfoss>DC Drives>VLT AutomationDrive FC 360

Danfoss VLT AutomationDrive FC 360 Programming Guide

Danfoss VLT AutomationDrive FC 360
340 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #67 background imageLoading...
Page #67 background image
Programming Guide | VLT® AutomationDrive FC 360
Use this parameter to set the inductance saturation point.
1-49 Current at Min Inductance for q-axis
Default value: 100% Parameter type: Range (20–200%)
Setup: All setups Conversion index: 0
Data type: Uint16 Change during operation: False
This parameter specifies the saturation curve of the q-inductance values. From 20–100% of this parameter, the inductance is linearly
approximated due to parameter 1-38 q-axis Inductance (Lq) and parameter 1-45 q-axis Inductance Sat. (LqSat). These parameters are
related to the motor nameplate load compensations, the application load type, and the electronic brake function for quick stop/hold of
the motor.
4.2.6 1-5* Load Indep. Setting
Parameters for load-independent motor settings.
1-50 Motor Magnetisation at Zero Speed
Default value: 100% Parameter type: Range (0–300%)
Setup: All setups Conversion index: 0
Data type: Uint16 Change during operation: True
Use this parameter along with parameter 1-52 Min Speed Normal Magnetising [Hz] to obtain a different thermal load on the motor when
running at low speed. Enter a value that is a percentage of the rated magnetizing current. If the setting is too low, the torque on the
motor shaft may be reduced.
Magn. current
90%
Par. 1-50
Par. 1-52
Hz
e30bb780.11
Figure 16: Motor Magnetization
1-52 Min Speed Normal Magnetising [Hz]
Default value: 1.0 Hz Parameter type: Range (0.1–10.0 Hz)
Setup: All setups Conversion index: -1
Data type: Uint16 Change during operation: True
Set the required frequency for normal magnetizing current. Use this parameter along with parameter 1-50 Motor Magnetisation at Zero
Speed.
1-53 Model Shift Frequency
Default value: Size related Parameter type: Range (4.0–65535.0 Hz)
Setup: All setups Conversion index: -1
Data type: Uint16 Change during operation: False
Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507 | 65

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 360

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 360 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 360 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 360
CategoryDC Drives
LanguageEnglish

Related product manuals