 NOTICE
This parameter is not active when parameter 1-10 Motor Construction is set to options that enable PM motor mode.
14-41 AEO Minimum Magnetisation
Default value: 40% Parameter type: Range (10%–100%)
Setup: All setups Conversion index: 0
Data type: Uint8 Change during operation: True
Enter the minimum allowable magnetization for AEO. Selection of a low value reduces energy loss in the motor, but can also reduce
resistance to sudden load changes.
14-42 Minimum AEO Frequency
Default value: Size related Parameter type: Range (0–255 Hz)
Setup: All setups Conversion index: 0
Data type: Uint8 Change during operation: True
Enter the minimum frequency at which the automatic energy optimization (AEO) is active.
14-44 d-axis current optimization for IPM
Default value: 100% Parameter type: Range (0–200%)
Setup: All setups Conversion index: 0
Data type: Uint8 Change during operation: True
This parameter is available only when parameter 1-10 Motor Construction is set to [3] PM, salient IPM. Normally, VVC+ PM control
automatically optimizes d-axis demagnetizing current based on d-axis and q-axis settings. When parameter 1-10 Motor Construction is
set to [3] PM, salient IPM, use this parameter to compensate the saturation effect at high load. Usually, decreasing this value improves
the efficiency. However, 0% means no optimization and the d-axis current is 0 (not recommended).
4.13.6 14-5* Environment
 NOTICE
Perform a power cycle after changing any of the parameters in parameter group 14-5* Environment.
These parameters help the drive to operate under special environmental conditions.
14-50 RFI Filter
Default value: [2] Grid Type Parameter type: Option
Setup: 1 setup Conversion index: –
Data type: Uint8 Change during operation: False
Select the RFI filter.
242 | Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507
Programming Guide | VLT® AutomationDrive FC 360