Programming Guide | VLT® AutomationDrive FC 360
Option Name Description
[0] Off Select [0] Off only when the drive is
connected to an isolated mains source (IT
mains).
[1] On Select [1] On to turn on the RFI filter. The
RFI filter ensures that the drive complies
with EMC standards.
[2] Grid Type
14-51 DC-Link Voltage Compensation
Default value: [1] On Parameter type: Option
Setup: All setups Conversion index: –
Data type: Uint8 Change during operation: False
Enable or disable the DC-link voltage compensation.
Option Name
[0] Off
[1] On
14-52 Fan Control
Default value: [5] Constant-on mode Parameter type: Option
Setup: 1 setup Conversion index: –
Data type: Uint8 Change during operation: True
Select the fan control mode.
Option Name
[5] Constant-on mode
[6] Constant-off mode
[7] On-when-Inverter-is-on-else-off Mode
[8] Variable-speed mode
14-55 Output Filter
Default value: [0] No Filter Parameter type: Option
Setup: 1 setup Conversion index: –
Data type: Uint8 Change during operation: False
Select the type of output filter connected.
Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507 | 243