Programming Guide | VLT® AutomationDrive FC 360
Option Name Description
[0] Digital input A digital input triggers the PROFIdrive
OFF2 selection.
[1] Bus A serial communication port or the
fieldbus triggers the PROFIdrive OFF2
selection.
[2] Logic AND The fieldbus/serial communication port
and a digital input trigger the PROFIdrive
OFF2 selection.
[3] Logic OR The fieldbus/serial communication port
or a digital input triggers the PROFIdrive
OFF2 selection.
8-58 PROFIdrive OFF3 Select
Default value: [3] Logic OR Parameter type: Option
Setup: All setups Conversion index: –
Data type: Uint8 Change during operation: True
Select control of the drive (digital input) and/or via the fieldbus. This parameter is active only when parameter 8-01 Control Site is set to
[0] Digital and ctrl. word and parameter 8-10 Control Word Profile is set to [1] PROFIdrive profile.
Option Name Description
[0] Digital input A digital input triggers the PROFIdrive
OFF3 selection.
[1] Bus A serial communication port or the
fieldbus triggers the PROFIdrive OFF3
selection.
[2] Logic AND The fieldbus/serial communication port
and a digital input trigger the PROFIdrive
OFF3 selection.
[3] Logic OR The fieldbus/serial communication port
or a digital input triggers the PROFIdrive
OFF3 selection.
4.9.6 8-7* Protocol SW Version
8-79 Protocol Firmware version
Default value: Size related Parameter type: Range (0.00–655.00), Array [5]
Setup: 1 setup Conversion index: -2
Data type: Uint16 Change during operation: False
Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507 | 183