Programming Guide | VLT® AutomationDrive FC 360
Option Name
[84] User Define11
[85] User Define12
[86] User Define13
[87] User Define14
[88] User Define15
[100] [1605] Main Actual Value [N2]
8-44 PCD User Define
Default value: 0 Parameter type: Range (0–65535), Array [16]
Setup: 1 setup Conversion index: 0
Data type: Uint16 Change during operation: True
Customize the User define X of parameter 8-42 PCD Write Configuration or parameter 8-43 PCD Read Configuration, [0-7] is for PCD
Write, [8-15] is for PCD Read.
4.9.5 8-5* Digital/Bus
Parameters for configuring the Digital/Bus merging.
 NOTICE
These parameters are active only when parameter 8-01 Control Site is set to [0] Digital and control word.
8-50 Coasting Select
Default value: [3] Logic OR Parameter type: Option
Setup: All setups Conversion index: –
Data type: Uint8 Change during operation: True
Select control of the coasting function via the terminals (digital input) and/or via the bus.
Option Name Description
[0] Digital input Activate coasting command via a digital
input.
[1] Bus Activate coasting command via the serial
communication port or fieldbus option.
[2] Logic AND Activate coasting command via the
fieldbus/serial communication port and 1
extra digital input.
[3] Logic OR Activate coasting command via the
fieldbus/serial communication port or via
1 of the digital inputs.
Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507 | 179