8-51 Quick Stop Select
Default value: [3] Logic OR Parameter type: Option
Setup: All setups Conversion index: –
Data type: Uint8 Change during operation: True
Select control of the quick stop function via the terminals (digital input) and/or via the bus.
Option Name Description
[0] Digital input Activate quick stop command via a digital
input.
[1] Bus Activate quick stop command via the
serial communication port or fieldbus
option.
[2] Logic AND Activate quick stop command via the
fieldbus/serial communication port and 1
extra digital input.
[3] Logic OR Activate quick stop command via the
fieldbus/serial communication port or via
1 of the digital inputs.
8-52 DC Brake Select
Default value: [3] Logic OR Parameter type: Option
Setup: All setups Conversion index: –
Data type: Uint8 Change during operation: True
Select control of the DC brake via the terminals (digital input) and/or via the bus.
 NOTICE
When parameter 1-10 Motor Construction is set to [1] PM non-salient SPM, only selection [0] Digital input is available.
Option Name Description
[0] Digital input Activate DC brake command via a digital
input.
[1] Bus Activate DC brake command via the serial
communication port or fieldbus option.
[2] Logic AND Activate DC brake command via the
fieldbus/serial communication port and 1
extra digital input.
[3] Logic OR Activate DC brake command via the
fieldbus/serial communication port or via
1 of the digital inputs.