Programming Guide | VLT® AutomationDrive FC 360
8-53 Start Select
Default value: [3] Logic OR Parameter type: Option
Setup: All setups Conversion index: –
Data type: Uint8 Change during operation: True
Select the trigger for the start function.
Option Name Description
[0] Digital input A digital input triggers the start function.
[1] Bus A serial communication port or the
fieldbus triggers the start function.
[2] Logic AND The fieldbus/serial communication
port and a digital input trigger the start
function.
[3] Logic OR The fieldbus/serial communication port or
a digital input triggers the start function.
8-54 Reversing Select
Default value: [3] Logic OR Parameter type: Option
Setup: All setups Conversion index: –
Data type: Uint8 Change during operation: True
Select the trigger for the reversing function.
Option Name Description
[0] Digital input A digital input triggers the reversing
function.
[1] Bus A serial communication port or the
fieldbus triggers the reversing function.
[2] Logic AND The fieldbus/serial communication port
and a digital input trigger the reversing
function.
[3] Logic OR The fieldbus/serial communication port
or a digital input triggers the reversing
function.
8-55 Set-up Select
Default value: [3] Logic OR Parameter type: Option
Setup: All setups Conversion index: –
Data type: Uint8 Change during operation: True
Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507 | 181