Option Name
[0] No Filter
[1] Sine-wave filter
4.13.7 14-6* Auto Derate
Use this parameter group to configure automatic derating for the output current of the drive.
14-61 Function at Inverter Overload
Default value: [0] Trip Parameter type: Option
Setup: All setups Conversion index: –
Data type: Uint8 Change during operation: True
When the drive issues a drive overload warning, select whether to continue and trip the drive, or derate the output current.
Option Name
[0] Trip
[1] Derate
14-63 Min Switch Frequency
Default value: [2] 2.0 kHz Parameter type: Option
Setup: 1 setup Conversion index: –
Data type: Uint8 Change during operation: False
Set the minimum switching frequency allowed by the output filter.
Option Name
[2] 2.0 kHz
[3] 3.0 kHz
[4] 4.0 kHz
[5] 5.0 kHz
[6] 6.0 kHz
[7] 8.0 kHz
[8] 10.0 kHz
[9] 12.0 kHz
[10] 16.0 kHz
244 | Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507
Programming Guide | VLT® AutomationDrive FC 360

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 360

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 360 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 360 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 360
CategoryDC Drives
LanguageEnglish

Related product manuals