Set the Gain Boost Factor.
2-29 Torque Ramp Down Time
Default value: 0.0 s Parameter type: Range (0.0–5.0 s)
Setup: All setups Conversion index: -1
Data type: Uint8 Change during operation: True
Set the torque ramp-down time.
4.3.4 2-3* Adv. Mech Brake
2-30 Position P Start Proportional Gain
Default value: 0.0000 Parameter type: Range (0.0000–1.0000)
Setup: All setups Conversion index: -4
Data type: Uint32 Change during operation: True
Enter the position controller during start proportional gain. Quick control is obtained at high amplification. However, if the amplification
is large, the process may become unstable.
2-31 Speed PID Start Proportional Gain
Default value: 0.015 Parameter type: Range (0.000 = Off–1.000)
Setup: All setups Conversion index: -3
Data type: Uint32 Change during operation: True
Enter the position controller during start proportional gain. Quick control is obtained at high amplification. However, if the amplification
is large, the process may become unstable.
2-32 Speed PID Start Integral Time
Default value: 200.0 ms Parameter type: Range (1.0 ms–20000.0 = Off
ms)
Setup: All setups Conversion index: -1
Data type: Uint32 Change during operation: True
Enter the speed controller integral time. Obtain quick control through a short integral time, if the integral time is short, the process
becomes unstable. An excessively long integral time disables the integral action.
2-33 Speed PID Start Lowpass Filter Time
Default value: 10.0 ms Parameter type: Range (0.1–100.0 ms)
Setup: All setups Conversion index: -1
Data type: Uint16 Change during operation: True
Set a time constant for the speed control low-pass filter. The low-pass filter improves steady-state performance and dampens oscillations
on the feedback signal. However, severe filtering can be detrimental to dynamic performance.
84 | Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507
Programming Guide | VLT® AutomationDrive FC 360

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 360

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 360 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 360 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 360
CategoryDC Drives
LanguageEnglish

Related product manuals