Programming Guide | VLT® AutomationDrive FC 360
Set the motor frequency for activation of the mechanical brake when a stop condition is present.
2-23 Activate Brake Delay
Default value: 0.0 s Parameter type: Range (0.0–5.0 s)
Setup: All setups Conversion index: -1
Data type: Uint8 Change during operation: True
Enter the brake delay time of the coast after ramp-down time. The shaft is held at 0 speed with full holding torque. Ensure that the
mechanical brake has locked the load before the motor enters coast mode.
2-24 Stop Delay
Default value: 0.0 s Parameter type: Range (0.0–5.0 s)
Setup: All setups Conversion index: -1
Data type: Uint8 Change during operation: True
It is used to define a time, during which the Speed closed loop controls the motor to run at 0 RPM. After that the brake is activated.
2-25 Brake Release Time
Default value: 0.00 s Parameter type: Range (0.00–5.00 s)
Setup: All setups Conversion index: -2
Data type: Uint16 Change during operation: True
It reserves a time before ramping up after opening the brake, and the Speed closed loop control controls the speed at 0 RPM.
2-26 Torque Ref
Default value: 0.00% Parameter type: Range (-300.00–300.00%)
Setup: All setups Conversion index: -2
Data type: Int16 Change during operation: True
Set the torque reference.
2-27 Torque Ramp Time
Default value: 0.2 s Parameter type: Range (0.0–5.0 s)
Setup: All setups Conversion index: -1
Data type: Uint8 Change during operation: True
Set the torque ramp time.
2-28 Gain Boost Factor
Default value: 1.00 Parameter type: Range (0.00–4.00)
Setup: All setups Conversion index: -2
Data type: Uint16 Change during operation: True
Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507 | 83