4.5.6 4-6* Speed Bypass
4-61 Bypass Speed From [Hz]
Default value: 0.0 Hz Parameter type: Range (0.0–500.0 Hz), Array [4]
Setup: All setups Conversion index: -1
Data type: Uint16 Change during operation: True
Some systems call for avoiding certain output speeds due to resonance problems in the system. Enter the lower limits of the speeds to
be avoided. The bypass speed from must not exceed the setting in parameter 4-14 Motor Speed High Limit [Hz].
4-63 Bypass Speed To [Hz]
Default value: 0.0 Hz Parameter type: Range (0.0–500.0 Hz), Array [4]
Setup: All setups Conversion index: -1
Data type: Uint16 Change during operation: True
Some systems call for avoiding certain output speeds due to resonance problems in the system. Enter the upper limits of the speeds to
be avoided. The bypass speed to must not exceed the setting in parameter 4-14 Motor Speed High Limit [Hz].
4.5.7 4-8* Power Limit
4-80 Power Limit Func. Motor Mode
Default value: [0] Disabled Parameter type: Option
Setup: All setups Conversion index: –
Data type: Uint8 Change during operation: True
The power limit motor mode is defined by parameter 4-82 Power Limit Motor Mode.
Option Name Description
[0] Disabled Disable the function.
[1] Enabled Enable the function.
[2] When Activated This option requires activation by digital
input or configurable control word.
4-81 Power Limit Func. Generator Mode
Default value: [0] Disabled Parameter type: Option
Setup: All setups Conversion index: –
Data type: Uint8 Change during operation: True
The power limit generator mode is defined by parameter 4-82 Power Limit Motor Mode.
108 | Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507
Programming Guide | VLT® AutomationDrive FC 360