Programming Guide | VLT® AutomationDrive FC 360
Setup: 1 setup Conversion index: -2
Data type: Int32 Change during operation: True
View the custom readout from parameter 0-30 Custom Readout Unit to parameter 0-32 Custom Readout Max Value.
4.15.2 16-1* Motor Status
16-10 Power [kW]
Default value: 0.000 kW Parameter type: Range (0.000–1000.000 kW)
Setup: 1 setup Conversion index: -3
Data type: Uint32 Change during operation: True
Show motor power in kW. The calculated value shown is based on the actual motor voltage and motor current. The value is filtered, and
therefore approximately 300 ms may pass from when an input value changes to when the data readout values change. The resolution of
readout value on fieldbus is in 10 W steps.
16-11 Power [hp]
Default value: 0.000 hp Parameter type: Range (0.000–1000.000 hp)
Setup: 1 setup Conversion index: -3
Data type: Uint32 Change during operation: True
View the motor power in hp. The value shown is calculated on the basis of the actual motor voltage and motor current. The value is
filtered, and therefore approximately 300 ms may pass from when an input value changes to when the data readout values change.
16-12 Motor Voltage
Default value: 0 V Parameter type: Range (0–65535 V)
Setup: 1 setup Conversion index: 0
Data type: Uint32 Change during operation: True
View the motor voltage. A calculated value is used for controlling the motor.
16-13 Frequency
Default value: 0.0 Hz Parameter type: Range (0.0–6553.5 Hz)
Setup: 1 setup Conversion index: -1
Data type: Uint32 Change during operation: True
View the motor frequency, without resonance damping.
16-14 Motor current
Default value: 0.00 A Parameter type: Range (0.00–655.35 A)
Setup: 1 setup Conversion index: -2
Data type: Uint16 Change during operation: True
Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507 | 255

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 360

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 360 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 360 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 360
CategoryDC Drives
LanguageEnglish

Related product manuals