Programming Guide | VLT® AutomationDrive FC 360
4.20.2 30-5* Unit Configuration
30-56 License Installed
Default value: – Parameter type: Range (0–40), Array [3]
Setup: 1 setup Conversion index: 0
Data type: VisStr Change during operation: False
Show the installed license. Index 0: Feature; Index 1: Maintenance; Index 2: Application.
30-57 License Code
Default value: – Parameter type: Range (0–19)
Setup: 1 setup Conversion index: 0
Data type: VisStr Change during operation: False
Enter the license code. The length of the license code is 19, for example: 1234-ABCD-5678-EFGH.
4.20.3 30-7* Power Monitoring
30-70 Power Low Monitoring
Default value: [0] Disabled Parameter type: Option
Setup: All setups Conversion index: –
Data type: Uint8 Change during operation: True
Power Low Monitoring (PLM) blocked rotor detection function.
Option Name
[0] Disabled
[1] Enabled
30-71 PLM Detection Time
Default value: 10.0 s Parameter type: Range (4.0–100.0 s)
Setup: All setups Conversion index: -1
Data type: Uint16 Change during operation: True
Power Low Monitoring (PLM) detection time window for power integration.
30-72 PLM Minimum Speed
Default value: 25% Parameter type: Range (10–100%)
Setup: All setups Conversion index: 0
Data type: Uint16 Change during operation: True
Power Low Monitoring (PLM) minimum detection speed above which the PLM algorithm is active.
Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507 | 281