Programming Guide | VLAutomationDrive FC 360
Setup: All setups Conversion index: 0
Data type: Int16 Change during operation: False
View the torque in percent of nominal torque, with sign, applied to the motor shaft.
16-24 Calibrated Stator Resistance
Default value: 0.0000 Ohm Parameter type: Range (0.0000–100.0000 Ohm)
Setup: All setups Conversion index: -4
Data type: Uint32 Change during operation: True
Show the calibrated stator resistance.
4.15.3 16-3* Drive Status
16-30 DC Link Voltage
Default value: 0 V Parameter type: Range (0–65535 V)
Setup: 1 setup Conversion index: 0
Data type: Uint32 Change during operation: True
View a measured value. The value is filtered with a 128 ms time constant.
16-33 Brake Energy /2 min
Default value: 0.000 kW Parameter type: Range (0.000–10000.000 kW)
Setup: All setups Conversion index: -3
Data type: Uint32 Change during operation: False
View the brake power sent to an external brake resistor. The average power is calculated on an average level based on the latest 120 s.
16-34 Heatsink Temp.
Default value: 0 °C Parameter type: Range (-128–127 °C)
Setup: 1 setup Conversion index: 0
Data type: Int8 Change during operation: True
View the drive heat sink temperature. The cutout limit is 90 ±5 °C [194 °F], and the motor cuts back in at 60 ±5 °C [140 °F].
16-35 Inverter Thermal
Default value: 0% Parameter type: Range (0–255%)
Setup: 1 setup Conversion index: 0
Data type: Uint8 Change during operation: True
View the percentage load on the inverter.
16-36 Inv. Nom. Current
Default value: 0.00 A Parameter type: Range (0.00–655.35 A)
Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507 | 257