Page #295 background image
Programming Guide | VLAutomationDrive FC 360
4.23.3 34-5* Process Data
Readout of process data for motion control.
34-50 Actual Position
Default value: 0 Parameter type: Range (-1073741824–
1073741824)
Setup: All setups Conversion index: 0
Data type: Int32 Change during operation: True
The actual position in user unit.
34-56 Track Error
Default value: 0 Parameter type: Range (-2147483647–
2147483647)
Setup: All setups Conversion index: 0
Data type: Int32 Change during operation: True
Readout of the error between calculated command position and actual position in user unit.
4.24 Parameter Group 35-** Sensor Input Option
4.24.1 More Information
NOTICE
Parameter Group 35-** Sensor Input Option is only valid when VLT® Sensor Input MCB 114 is installed.
4.24.2 35-0* Temp. Input Mode
35-01 Term. X48/4 Input Type
Default value: [0] Not Connected Parameter type: Option
Setup: All setups Conversion index:
Data type: Uint8 Change during operation: True
View the temperature sensor type detected at input X48/4.
Option Name
[0] Not Connected
[1] PT100 2-wire
[3] PT1000 2-wire
[5] PT100 3-wire
[7] PT1000 3-wire
Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507 | 293

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 360

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 360 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 360 Specifications

General IconGeneral
CategoryDC Drives
Output Voltage0 to Input Voltage
Control MethodV/f, Vector Control
Communication ProtocolsModbus RTU
Enclosure RatingIP20
Brake chopperBuilt-in
EMCCompliant with EN 61800-3
Protection FeaturesOvercurrent, overvoltage, undervoltage, short circuit, overtemperature
Ambient Temperature-10 to +50 °C
Storage Temperature-25 to +70 °C
Relative Humidity5 - 95% non-condensing
AltitudeUp to 1000 m
Input Voltage380 to 480 V