Setup: 1 setup Conversion index: -2
Data type: Uint16 Change during operation: True
View the inverter nominal current, which should match the nameplate data on the connected motor. The data is used for calculation of
torque and motor overload protection.
16-37 Inv. Max. Current
Default value: 0.00 A Parameter type: Range (0.00–655.35 A)
Setup: 1 setup Conversion index: -2
Data type: Uint16 Change during operation: True
View the inverter maximum current, which should match the nameplate data on the connected motor. The data is used for calculation of
torque and motor overload protection.
16-38 SL Controller State
Default value: 0 Parameter type: Range (0–20)
Setup: 1 setup Conversion index: 0
Data type: Uint8 Change during operation: True
View the state of the event under execution by the SL Controller.
16-39 Control Card Temp.
Default value: 0 °C Parameter type: Range (0–65535 °C)
Setup: All setups Conversion index: 0
Data type: Uint16 Change during operation: False
View the temperature on the control card, stated in °C.
16-48 Speed Ref. After Ramp [RPM]
Default value: 0 RPM Parameter type: Range (-30000–30000 RPM)
Setup: All setups Conversion index: 0
Data type: Int32 Change during operation: False
Define the reference given to the drive after the speed ramp in RPM.
4.15.4 16-5* Ref. & Feedb.
16-50 External Reference
Default value: 0.0% Parameter type: Range (-200.0–200.0%)
Setup: 1 setup Conversion index: -1
Data type: Int16 Change during operation: True
View the total reference, the sum of digital, analog, preset, bus, and freeze references, plus catch up and slow down.