4.6.4 5-4* Relays
Parameters for configuring the timing and the output functions for the relays.
The parameter is an array parameter showing 2 relays: Array [2] (Relay 1 [0], Relay 2 [1]).
5-40 Function Relay
Default value: Size related Parameter type: Option, Array [2]
Setup: All setups Conversion index: –
Data type: Uint8 Change during operation: True
Select the function to control the output relays.
Option Name Description
[0] No operation Default for all digital outputs and relay
outputs.
[1] Control Ready The control card is ready.
[2] Drive ready The drive is ready to operate. Mains and
control supplies are OK.
[3] Drive rdy/rem ctrl The drive is ready for operation and is in
auto-on mode.
[4] Stand-by/no warning Ready for operation. No start or stop
command is given (start/disable). No
warnings are active.
[5] Running The motor is running and shaft torque is
present.
[6] Running/no warning The motor is running and there are no
warnings.
[7] Run in range/no warn The motor is running within the
programmed current and speed ranges
set in parameter 4-50 Warning Current
Low to parameter 4-51 Warning Current
High. There are no warnings.
[8] Run on ref/no warn The motor runs at reference speed. No
warnings.
[9] Alarm An alarm activates the output.
[10] Alarm or warning An alarm or a warning activates the
output.
[11] At torque limit The torque limit set in parameter 4-16
Torque Limit Motor Mode or parameter
4-17 Torque Limit Generator Modehas
been exceeded.
[12] Out of current range The motor current is outside the range set
in parameter 4-18 Current Limit.