4.24.4 35-2* Temp. Input X48/7
35-24 Term. X48/7 Filter Time Constant
Default value: 0.005 s Parameter type: Range (0.005–10.000 s)
Setup: All setups Conversion index: -3
Data type: Uint16 Change during operation: True
Enter the filter time constant. This is a first-order digital lowpass filter time constant for suppressing electrical noise in terminal X48/7. A
high time constant value improves dampening but also increases the time delay through the filter.
35-25 Term. X48/7 Temp. Monitor
Default value: [0] Disabled Parameter type: Option
Setup: All setups Conversion index: –
Data type: Uint8 Change during operation: True
This parameter gives the possibility of enabling or disabling the temperature monitor for terminal X48/7. The temperature limits can be
set in parameter 35-26 Term. X48/7 Low Temp. Limit/parameter 35-27 Term. X48/7 High Temp. Limit.
Option Name
[0] Disabled
[1] Enabled
35-26 Term. X48/7 Low Temp. Limit
Default value: -50 Parameter type: Range (-50–204)
Setup: All setups Conversion index: 0
Data type: Int16 Change during operation: True
Enter the minimum temperature reading that is expected for normal operation of the temperature sensor at terminal X48/7.
35-27 Term. X48/7 High Temp. Limit
Default value: 204 Parameter type: Range (-50–204)
Setup: All setups Conversion index: 0
Data type: Int16 Change during operation: True
Enter the maximum temperature reading that is expected for normal operation of the temperature sensor at terminal X48/7.
4.24.5 35-3* Temp. Input X48/10
35-34 Term. X48/10 Filter Time Constant
Default value: 0.005 s Parameter type: Range (0.005–10.000 s)
Setup: All setups Conversion index: -3
Data type: Uint16 Change during operation: True