Programming Guide | VLAutomationDrive FC 360
8-85 Slave Timeout Errors
Default value: 0 Parameter type: Range (0–4294967295)
Setup: 1 setup Conversion index: 0
Data type: Uint32 Change during operation: True
Show the number of slave timeout errors.
8-88 Reset FC port Diagnostics
Default value: [0] Do not reset Parameter type: Option
Setup: 1 setup Conversion index:
Data type: Uint8 Change during operation: True
Reset all FC port diagnostic counters.
Option Name
[0] Do not reset
[1] Reset counter
4.9.8 8-9* Bus Feedback
Use the parameter group to configure the bus feedback.
8-90 Bus Jog 1 Speed
Default value: 100 RPM Parameter type: Range (0–1500 RPM)
Setup: All setups Conversion index: 0
Data type: Uint16 Change during operation: True
Enter the jog speed. This is a fixed jog speed activated via the serial port or fieldbus option.
8-91 Bus Jog 2 Speed
Default value: 200 RPM Parameter type: Range (0–1500 RPM)
Setup: All setups Conversion index: 0
Data type: Uint16 Change during operation: True
Enter the jog speed. This is a fixed jog speed activated via the serial port or fieldbus option.
4.10 Parameter Group 9-** PROFIdrive
For more information about PROFIBUS parameter descriptions, see the VLT® AutomationDrive FC 360 PROFIBUS DP Programming Guide.
For more information about PROFINET parameter descriptions, see the VLT® AutomationDrive FC 360 PROFINET Programming Guide.
NOTICE
Some parameters in this chapter are only for PROFIBUS, and some parameters are only for PROFINET.
Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507 | 185