Select the input to which the thermistor (PTC sensor) should be connected. If an analog input in this parameter is set as a source, it
cannot be used for another purpose, for example, reference or feedback.
 NOTICE
Digital input should be set to [0] PNP - Active at 24 V in parameter 5-00 Digital Input Mode.
Option Name
[0] None
[1] Analog Input 53
[2] Analog Input 54
[3] Digital input 18
[4] Digital input 19
[5] Digital input 32
[6] Digital input 33
[7] Digital input 31
4.3 Parameter Group 2-** Brakes
4.3.1 2-0* DC-Brake
Use this parameter group to configure DC brake and DC hold functions.
2-00 DC Hold/Motor Preheat Current
Default value: 50% Parameter type: Range (0–160%)
Setup: All setups Conversion index: 0
Data type: Uint16 Change during operation: True
Set the holding current as a percentage of the rated motor current I
M,N
parameter 1-24 Motor Current. This parameter holds the motor
function (holding torque) or pre-heats the motor. This parameter is active if [0] DC hold is selected in parameter 1-72 Start Function, or if
[1] DC hold/preheatis selected in parameter 1-80 Function at Stop.
 NOTICE
The maximum value depends on the rated motor current. Avoid 100% current for too long. It may damage the motor.
2-01 DC Brake Current
Default value: 50% Parameter type: Range (0–150%)
Setup: All setups Conversion index: 0
Data type: Uint16 Change during operation: True
78 | Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507
Programming Guide | VLT® AutomationDrive FC 360