6-25 Terminal 54 High Ref./Feedb. Value
Default value: Size related Parameter type: Range (-4999.000–4999.000)
Setup: All setups Conversion index: -3
Data type: Int32 Change during operation: True
Enter the reference or feedback value that corresponds to the voltage or current set in parameter 6-21 Terminal 54 High
Voltage/parameter 6-23 Terminal 54 High Current.
6-26 Terminal 54 Filter Time Constant
Default value: 0.01 s Parameter type: Range (0.01–10.00 s)
Setup: All setups Conversion index: -2
Data type: Uint16 Change during operation: True
Enter the time constant, which is a first order digital low-pass filter time constant for suppressing electrical noise in terminal 54. A high
time constant value improves dampening, but also increases the time delay through the filter.
6-29 Terminal 54 mode
Default value: [1] Voltage mode Parameter type: Option
Setup: 1 setup Conversion index: –
Data type: Uint8 Change during operation: True
Select if terminal 54 is used for current input or voltage input.
Option Name
[0] Current mode
[1] Voltage mode
4.7.5 6-7* Analog/Digital Output 45
Parameters for configuring the scaling and limits for analog/digital output terminal 45. Analog outputs are current outputs: 0/4–20 mA.
Resolution on analog output is 12 bit. Analog output terminals can also be set up as digital output.
6-70 Terminal 45 Mode
Default value: [0] 0-20 mA Parameter type: Option
Setup: All setups Conversion index: –
Data type: Uint8 Change during operation: True
Set terminal 45 to act as analog output or as digital output.