Option Name Description
[0] Off Link speed and link duplex can be
configured in parameter 12-13 Link Speed
and parameter 12-14 Link Duplex.
[1] On
12-13 Link Speed
Default value: [0] None Parameter type: Option, Array [2]
Setup: 1 setup Conversion index:
Data type: Uint8 Change during operation: True
Forces the link speed for each port in 10 Mbps or 100 Mbps. If parameter 12-12 Auto Negotiation is set to [1] On, this parameter is read-
only and shows the actual link speed. If no link is present, None is shown.
Option Name
[0] None
[1] 10 Mbps
[2] 100 Mbps
12-14 Link Duplex
Default value: [1] Full Duplex Parameter type: Option, Array [2]
Setup: 1 setup Conversion index:
Data type: Uint8 Change during operation: True
Forces the duplex for each port to full or half duplex. If parameter 12-12 Auto Negotiation is set to [1] On, this parameter is read-only.
Option Name
[0] Half Duplex
[1] Full Duplex
4.11.4 12-8* Other Ethernet Services
12-80 FTP Server
Default value: [0] Disabled Parameter type: Option
Setup: 1 setup Conversion index:
Data type: Uint8 Change during operation: True
Enable or disable the built-in FTP server.
206 | Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507