7-36 Process PID Diff. Gain Limit
Default value: 5.0 Parameter type: Range (1.0–50.0)
Setup: All setups Conversion index: -1
Data type: Uint16 Change during operation: True
Enter a limit for the differentiator gain. If there is no limit, the differentiator gain increases when there are fast changes. To obtain a pure
differentiator gain at slow changes and a constant differentiator gain where fast changes occur, limit the differentiator gain.
7-38 Process PID Feed Forward Factor
Default value: 0% Parameter type: Range (0–200%)
Setup: All setups Conversion index: 0
Data type: Uint16 Change during operation: True
Enter the PID feedforward (FF) factor. The FF factor sends a constant fraction of the reference signal to bypass the PID control, so the
PID control only affects the remaining fraction of the control signal. Any change to this parameter affects the motor speed. When the FF
factor is activated, it provides less overshoot, and high dynamics when changing the setpoint. Parameter 7-38 Process PID Feed Forward
Factor is active when parameter 1-00 Configuration Mode is set to [3] Process.
7-39 On Reference Bandwidth
Default value: 5% Parameter type: Range (0–200%)
Setup: All setups Conversion index: 0
Data type: Uint8 Change during operation: True
Enter the on-reference bandwidth. When the PID control error (the difference between the reference and the feedback) is less than the
value of this parameter, the on-reference status bit is 1.
4.8.5 7-4* Adv. Process PID I
This parameter group is only used if parameter 1-00 Configuration Mode is set to [7] Extended PID speed CL.
7-40 Process PID I-part Reset
Default value: [0] No Parameter type: Option
Setup: All setups Conversion index: –
Data type: Uint8 Change during operation: True
Select [1] Yes to reset the I-part of the Process PID Controller. The selection automatically reverts to [0] No. Resetting the I-part makes it
possible to start from a well-defined point after changing something in the process, for example changing a textile roll.
Option Name
[0] No
[1] Yes
166 | Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507
Programming Guide | VLT® AutomationDrive FC 360

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 360

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 360 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 360 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 360
CategoryDC Drives
LanguageEnglish

Related product manuals