Data type: Uint16 Change during operation: True
Set the time for which the broken belt conditions must be active before carrying out the action selected in parameter 22-60 Broken Belt
Function.
4.20 Parameter Group 30-** Special Features
4.20.1 30-2* Adv. Start Adjust
30-20 High Starting Torque Time [s]
Default value: Size related Parameter type: Range (0.00–60.00 s)
Setup: All setups Conversion index: -2
Data type: Uint16 Change during operation: True
High starting torque time for PM motors in VVC+ mode without feedback.
30-21 High Starting Torque Current [%]
Default value: Size related Parameter type: Range (0.0–200.0%)
Setup: All setups Conversion index: -1
Data type: Uint32 Change during operation: True
High starting torque current for PM motors in VVC+ mode without feedback.
30-22 Locked Rotor Protection
Default value: [0] Off Parameter type: Option
Setup: All setups Conversion index: –
Data type: Uint8 Change during operation: True
Locked rotor detection for PM motor.
Option Name
[0] Off
[1] On
30-23 Locked Rotor Detection Time [s]
Default value: 0.10 s Parameter type: Range (0.05–1.00 s)
Setup: All setups Conversion index: -2
Data type: Uint8 Change during operation: True
Locked rotor detection time for PM motor.