Programming Guide | VLT® AutomationDrive FC 360
[51] Comparator 5
[60] Logic rule 4
[61] Logic rule 5
[70] SL Time-out 3
[71] SL Time-out 4
[72] SL Time-out 5
[73] SL Time-out 6
[74] SL Time-out 7
[83] Broken Belt
13-03 Reset SLC
Default value: [0] Do not reset SLC Parameter type: Option
Setup: 1 setup Conversion index: –
Data type: Uint8 Change during operation: True
Reset all parameters in parameter group 13-** Smart Logic to default settings.
Option Name Description
[0] Do not reset SLC Do not reset the parameters in parameter
group 13-** Smart Logic.
[1] Reset SLC Reset all parameters in parameter group
13-** Smart Logic to default settings.
4.12.3 13-1* Comparators
Comparators are used for comparing continuous variables (that is output frequency, output current, analog input, and so on.) to fixed
preset values.
Comparator Operator
=
TRUE longer than.
. . .
. . .
Par. 13-10
Comparator Operand
Par. 13-12
Comparator Value
e30bb672.10
Figure 41: Comparators
There are digital values that are compared to fixed time values. See explanation in parameter 13-10 Comparator Operand. Comparators
are evaluated once in each scan interval. Use the result (true or false) directly. All parameters in this parameter group are array
parameters with index 0 to 5. Select index 0 to program comparator 0, select index 1 to program comparator 1, and so on.
Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507 | 215