Firmware revision for local bus protocols.
l FC is in index 0;
l Modbus is in index 1;
l Indexes 2–4 are reserved.
4.9.7 8-8* FC Port Diagnostics
These parameters are used for monitoring the bus communication via the drive port.
8-80 Bus Message Count
Default value: 0 Parameter type: Range (0–4294967295)
Setup: 1 setup Conversion index: 0
Data type: Uint32 Change during operation: True
Show the number of valid telegrams detected on the bus.
8-81 Bus Error Count
Default value: 0 Parameter type: Range (0–4294967295), Array
[6]
Setup: 1 setup Conversion index: 0
Data type: Uint32 Change during operation: True
Show the number of telegrams with faults (for example CRC faults) detected on the bus.
8-82 Slave Messages Rcvd
Default value: 0 Parameter type: Range (0–4294967295)
Setup: 1 setup Conversion index: 0
Data type: Uint32 Change during operation: True
Show the number of valid telegrams sent by the drive to the slave.
8-83 Slave Error Count
Default value: 0 Parameter type: Range (0–4294967295)
Setup: 1 setup Conversion index: 0
Data type: Uint32 Change during operation: True
Show the number of error telegrams, which could not be executed by the drive.
8-84 Slave Messages Sent
Default value: 0 Parameter type: Range (0–4294967295)
Setup: 1 setup Conversion index: 0
Data type: Uint32 Change during operation: True
Show the number of messages sent from the slave.