Programming Guide | VLT® AutomationDrive FC 360
Set current as % of rated motor current, parameter 1-24 Motor Current. When the speed is below the limit set in parameter 2-04 DC Brake
Cut In Speed, or when the DC brake inverse function is active (in parameter group 5-1* Digital Inputs set to [5] DC-brake inverse; or via
the serial port), a DC brake current is applied on a stop command. See parameter 2-02 DC Braking Time for duration.
 NOTICE
MOTOR OVERHEATING
The maximum value depends on the rated motor current.
l To avoid motor damage caused by overheating, do not run at 100% for too long.
2-02 DC Braking Time
Default value: 10.0 s Parameter type: Range (0.0–60.0 s)
Setup: All setups Conversion index: 0
Data type: Uint16 Change during operation: True
Set the duration of the DC brake current set in parameter 2-01 DC Brake Current, once activated.
2-04 DC Brake Cut In Speed
Default value: 0.0 Hz Parameter type: Range (0.0–par. 4-14 Hz)
Setup: All setups Conversion index: -1
Data type: Uint16 Change during operation: True
This parameter is for setting the DC brake cut-in speed at which the DC brake current parameter 2-01 DC Brake Current is to be active,
with a stop command.
2-06 Parking Current
Default value: 100% Parameter type: Range (0–150%)
Setup: All setups Conversion index: 0
Data type: Uint16 Change during operation: True
Set current as percentage of rated motor current, parameter 1-24 Motor Current.
Before setting this parameter, select [1] Parking in parameter 1-70 Start Mode.
2-07 Parking Time
Default value: 3.0 s Parameter type: Range (0.1–60.0 s)
Setup: All setups Conversion index: -1
Data type: Uint16 Change during operation: True
Set the duration of the parking current set in parameter 2-06 Parking Current, once activated.
4.3.2 2-1* Brake Energy Funct.
Parameter group for selecting dynamic braking parameters. Only valid for drives with brake chopper.