Programming Guide | VLT® AutomationDrive FC 360
Set current as % of rated motor current, parameter 1-24 Motor Current. When the speed is below the limit set in parameter 2-04 DC Brake
Cut In Speed, or when the DC brake inverse function is active (in parameter group 5-1* Digital Inputs set to [5] DC-brake inverse; or via
the serial port), a DC brake current is applied on a stop command. See parameter 2-02 DC Braking Time for duration.
 NOTICE
MOTOR OVERHEATING
The maximum value depends on the rated motor current.
l To avoid motor damage caused by overheating, do not run at 100% for too long.
2-02 DC Braking Time
Default value: 10.0 s Parameter type: Range (0.0–60.0 s)
Setup: All setups Conversion index: 0
Data type: Uint16 Change during operation: True
Set the duration of the DC brake current set in parameter 2-01 DC Brake Current, once activated.
2-04 DC Brake Cut In Speed
Default value: 0.0 Hz Parameter type: Range (0.0–par. 4-14 Hz)
Setup: All setups Conversion index: -1
Data type: Uint16 Change during operation: True
This parameter is for setting the DC brake cut-in speed at which the DC brake current parameter 2-01 DC Brake Current is to be active,
with a stop command.
2-06 Parking Current
Default value: 100% Parameter type: Range (0–150%)
Setup: All setups Conversion index: 0
Data type: Uint16 Change during operation: True
Set current as percentage of rated motor current, parameter 1-24 Motor Current.
Before setting this parameter, select [1] Parking in parameter 1-70 Start Mode.
2-07 Parking Time
Default value: 3.0 s Parameter type: Range (0.1–60.0 s)
Setup: All setups Conversion index: -1
Data type: Uint16 Change during operation: True
Set the duration of the parking current set in parameter 2-06 Parking Current, once activated.
4.3.2 2-1* Brake Energy Funct.
Parameter group for selecting dynamic braking parameters. Only valid for drives with brake chopper.
Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507 | 79

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 360

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 360 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 360 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 360
CategoryDC Drives
LanguageEnglish

Related product manuals