EasyManua.ls Logo

Danfoss VLT AutomationDrive FC 360

Danfoss VLT AutomationDrive FC 360
340 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Programming Guide | VLAutomationDrive FC 360
1-15 Low Speed Filter Time Const.
Default value: Size related Parameter type: Range (0.01–20.00 s)
Setup: All setups Conversion index: -2
Data type: Uint16 Change during operation: True
This time constant is used below 10% rated speed. Obtain quick control through a short damping time constant. However, if this value is
too short, the control becomes unstable.
1-16 High Speed Filter Time Const.
Default value: Size related Parameter type: Range (0.01–20.00 s)
Setup: All setups Conversion index: -2
Data type: Uint16 Change during operation: True
This time constant is used above 10% rated speed. Obtain quick control through a short damping time constant. However, if this value is
too short, the control becomes unstable.
1-17 Voltage Filter Time Const.
Default value: Size related Parameter type: Range (0.001–1.000 s)
Setup: All setups Conversion index: -3
Data type: Uint16 Change during operation: True
Reduces the influence of high frequency ripple and system resonance in the calculation of supply voltage. Without this filter, the ripples
in the currents can distort the calculated voltage and affect the stability of the system.
1-18 Min. Current at No Load
Default value: 0% Parameter type: Range (0–50%)
Setup: All setups Conversion index: 0
Data type: Uint16 Change during operation: True
Adjust the "Isd" current in no load situations to achieve a smoother motor operation.
4.2.3 1-2* Motor Data
This parameter group comprises input data from the nameplate on the connected motor.
NOTICE
Changing the value of these parameters affects the setting of other parameters.
1-20 Motor Power
Default value: Size related Parameter type: Option
Setup: All setups Conversion index:
Data type: Uint8 Change during operation: False
Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507 | 57

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 360

Related product manuals