Programming Guide | VLT® AutomationDrive FC 360
Data type: Int32 Change during operation: True
Use this parameter to set a low limit for the feedback range. When the feedback drops below this limit, the display shows Feedb Low. Bit
6 is set in parameter 16-94 Ext. Status Word. The output relay or the digital output can be configured to indicate this warning. The LCP
warning indicator light is not turned on when this parameter set limit is reached.
4-57 Warning Feedback High
Default value: 4999.000 ProcessCtrlUnit Parameter type: Range (-4999.000–4999.000
ProcessCtrlUnit)
Setup: All setups Conversion index: -3
Data type: Int32 Change during operation: True
Use this parameter to set a high limit for the feedback range. When the feedback exceeds this limit, the display reads Feedb High. Bit 5
is set in parameter 16-94 Ext. Status Word. The output relay or the digital output can be configured to indicate this warning. The LCP
warning indicator light is not turned on when this parameter set limit is reached.
4-58 Missing Motor Phase Function
Default value: [1] Trip 10s Parameter type: Option
Setup: All setups Conversion index: –
Data type: Uint8 Change during operation: False
Turn on the missing motor phase function or trip.
Option Name
[0] Off
[1] Trip 10s
[6] Trip 1s 3ph detec.
4-59 Motor Check At Start
Default value: [0] Off Parameter type: Option
Setup: All setups Conversion index: –
Data type: Uint8 Change during operation: True
3-phase motor check at start.
Option Name
[0] Off
[1] On
Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507 | 107