This parameter is active only when parameter 1-10 Motor Construction is set to [3] PM, salient IPM. This parameter corresponds to the
saturation inductance of d-axis. The default value is the value set in parameter 1-37 d-axis Inductance (Ld). In most cases, do not change
the default value. If the motor supplier provides the saturation curve, enter the d-axis inductance value, which is under 100% of the
nominal current or perform an AMA on a cold motor.
1-45 q-axis Inductance Sat. (LqSat)
Default value: Size related Parameter type: Range (0.001–65535.000 mH)
Setup: All setups Conversion index: -3
Data type: Int32 Change during operation: False
This parameter is active only when parameter 1-10 Motor Construction is set to [3] PM, salient IPM. This parameter corresponds to the q-
axis saturation inductance. The default value is the value set in parameter 1-38 q-axis Inductance (Lq). In most cases, do not change the
default value. If the motor supplier provides the saturation curve, enter the q-axis inductance value, which is under 100% of the nominal
current or perform an AMA on a cold motor.
1-46 Position Detection Gain
Default value: 100% Parameter type: Range (20–200%)
Setup: All setups Conversion index: 0
Data type: Uint16 Change during operation: True
Adjust the amplitude of the test pulse during position detection at start. Adjust this parameter to improve the position measurement.
1-47 Low Speed Torque Calibration
Default value: [0] Off Parameter type: Option
Setup: All setups Conversion index: –
Data type: Uint8 Change during operation: True
Measure the actual losses during start to optimize the torque estimate at low speed.
Option Name
[0] Off
[1] 1st start after pwr-up
[2] Every start
[3] 1st start with store
[4] Every start with store
1-48 Current at Min Inductance for d-axis
Default value: 100% Parameter type: Range (20–200%)
Setup: All setups Conversion index: 0
Data type: Int16 Change during operation: False
64 | Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507
Programming Guide | VLT® AutomationDrive FC 360

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 360

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 360 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 360 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 360
CategoryDC Drives
LanguageEnglish

Related product manuals