1-64 Resonance Dampening
Default value: Size related Parameter type: Range (0–500%)
Setup: All setups Conversion index: 0
Data type: Uint16 Change during operation: True
Enter the resonance dampening value. Set parameter 1-64 Resonance Dampening and parameter 1-65 Resonance Dampening Time
Constant to help eliminate high-frequency resonance problems. To reduce resonance oscillation, increase the value of parameter 1-64
Resonance Dampening.
1-65 Resonance Dampening Time Constant
Default value: 0.005 s Parameter type: Range (0.001–0.050 s)
Setup: All setups Conversion index: -3
Data type: Uint16 Change during operation: True
Set parameter 1-64 Resonance Dampening and parameter 1-65 Resonance Dampening Time Constant to help eliminate high-frequency
resonance problems. Enter the time constant that provides the best dampening.
1-66 Min. Current at Low Speed
Default value: Size related Parameter type: Range (0–120%)
Setup: All setups Conversion index: 0
Data type: Uint32 Change during operation: True
Enter the minimum motor current at low speed. Increasing this current improves motor torque at low speed. Parameter 1-66 Min.
Current at Low Speed is enabled only for PM motor.
1-67 Load Type
Default value: [0] Passive load Parameter type: Option
Setup: All setups Conversion index:
Data type: Uint8 Change during operation: True
Select the load type.
Option Name
[0] Passive load
[1] Active load
1-68 Motor Inertia
Default value:
0.0000 kgm
2
Parameter type: Range (0.0000–10000.0000
kgm
2
)
Setup: All setups Conversion index: -4
Data type: Uint32 Change during operation: False
68 | Danfoss A/S © 2024.01 AU275649936274en-001401 / 130R0507
Programming Guide | VLAutomationDrive FC 360